Visio-3 Specifications
General
Alarm Screens
Analog Inputs
Analog Outputs
Repeat Outputs
Remote Mute Input
Door Interlock
Alarm Contacts
Aux Power Supply
Audible Alarm
Alarm Messages
Control Options
Password Access
Datalogs
Display Options
Room Description
Mounting Options
----Uses traffic light colouring (Green-Amber-Red)
----3 No inputs (4-20mA & 0-10Volt
----3 No outputs (0-10Volts)
----3 No Outputs (0-10 Volts)
----Volt-free contact to be used
----Volt-free contact to be used
----3 No Volt-free contacts (N/O & N/C)
----24 Volt AC for sensors & actuator drive
----Specific sound for each input channel
----Choice of up to 9 pre-programmed messages
----Reverse & Forward loop control for each output
----2 levels of access (Operator & Engineering)
----Up to 12 hours realtime at 10min intervals
----2 homepage configurations
----Customisable room name via onscreen keyboard
----Flush fitting for wall or control panel.
Electrical
Power Supply
Power Consumption
Electrical Connections
Cable Glanding
Fuse Rating
Alarm Contacts
Analog Inputs
Analog Outputs
Comms Cable
----24 Volt AC/DC +/- 10% (0v to earth)
----12 VA
----CSA of 1.5mm or 15 AWG
----Termination box has 8 No 20mm knockouts
----2 Amp (This is only used for sensors & drives)
----10 Amp @ 250 Volts AC
----4-20mA or 0-10 Volt DC
----0-10 Volts DC
----26 pin sub-D connectors
Display
Display Type
Resolution
Colour Depth
Brightness
----Resistive touchscreen with LED backlighting
----640 X 480
----32bit
----290 CD/M2 (Dims on no activity)
Dimensions (Flush Mounting)
Whats in the Box
Connection Box
Connection Box
Compliance
Radiated Emissions:
Radiated Immunity:
EN55011
61326-1
EN61000-4-2:2009
EN61000-4-3:2006
EN61000-4-4:2012
EN61000-4-6:2014
EN61000-4-8:2010